Direct naar de inhoud
⚡ Kritieke cyberalerts voor jouw sector & systemen — direct in je inbox. Aanmelden →
CVE's Videos Dagbriefing

← Terug naar CVE-database

CVE-2026-3611

CRITICAL · 10.0 CVSS Gepubliceerd: CWE-306

Beschrijving

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Vendors

Honeywell

Affected products

Iq4e Firmware Iq4e Iq412 Firmware Iq412 Iq422 Firmware Iq422 Iq4nc Firmware Iq4nc Iq41x Firmware Iq41x

References